1A DIVISION OF A.O. SMITH CORPORATIONMc BEE, SOUTH CAROLINAPLACE THESE INSTRUCTIONS ADJACENT TO HEATER ANDNOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.PR
10FIGURE 12INSTALLATION OF VENT SYSTEM WARNINGTHE OPTIONAL INTAKE VENTING ARRANGEMENT AND THE EXHAUSTVENTING ARRANGEMENT MUST BE INSTALLED TO RUN DIRE
11D. Know your own qualifications or those of your contractor. Thesolvent welding technique of joining PVC, PVC cellular core, ABS orCPVC pipe is a sp
12BLOCKED OUTLET PROVER SWITCH(SEE FIGURE 13)The Blocked Outlet Prover Switch is set up to shut the unit off when a build-up of positive pressure in t
13CONNECTION OF GAS PIPE1. When connecting gas pipe to unit, apply wrench to flange only. Note:Do not use wrench on gas valve or gas bracket. See Fig
144. When the system requires water for space heating at temperatureshigher than required for domestic water purposes, a tempering valvemust be instal
15OPERATIONSEQUENCE OF OPERATIONTypical Control/Appliance Operating Sequence1. When the control is initially powered, it enters a test mode and willdi
16NO LOW VOLTAGE (Figure 20)24V AC LED OffNO LOW VOLTAGE, 24V AC LED OffFIGURE 20TEMPERATURE PROBE FAULT (Figure 21)Water Temp LED FlashingTEMPERATURE
17Display Flashes “05” when button is pressed:Display Flashes “15” when button is pressed:Display Flashes “25” when button is pressed:ECO SWITCH OPEN
18ADJUSTMENT PROCEDUREINITIAL START-UPA minimum gas supply pressure of 5.0" (1.25 kPa) W.C. (4.5" or 1.12 kPa)on BTH 150 and 199) for natur
19FOR YOUR SAFETY READ BEFORE OPERATINGWARNING: If you do not follow these instructions exactly, a fire orexplosion may result causing property damag
2These designs comply with the latest version of the American NationalStandard for Gas Water Heaters, Volume III, ANSI Z21.10.3 / CSA 4.3 M 98as an au
20 WARNINGUNDER NO CIRCUMSTANCES SHOULD THE INPUT EXCEED THE RATESHOWN ON THE HEATER RATING PLATE. OVERFIRING COULD RESULTIN DAMAGE OR SOOTING OF THE
21FIGURE 25To dissolve and remove the more stubborn mineral deposits, A.O. SmithUN•LIME® Professional Delimer should be used.A.O. Smith UN•LIME® Profe
22To inspect or replace an anode:The anodes on this heater are easily accessible from the top of theheater making replacement simple and quick.1. Turn
23ONE TEMPERATURE - ONE HEATER HORIZONTAL STORAGE TANKFORCED CIRCULATION WITH OR WITHOUT BUILDING RECIRCULATION DANGERTEMPERATURE SETTING SHOULD NOT E
24*PIPE RELIEF VALVE TO OPEN DRAIN.NOTE: IF TEMPERED WATER ISRECIRCULATED, RETURN LINE SHOULD BECONNECTED AT POINT “A”.INSTALL IN ACCORDANCE WITH LO
25TWO TEMPERATURE - TWO HEATERS HIGH TEMPERATUREWITH OR WITHOUT BUILDING RECIRCULATIONTWO TEMPERATURE - THREE HEATERS (TWO PRE-HEATERS/ONE BOOSTER HEA
26* PIPE RELIEF VALVE TO OPEN DRAIN** 140°F (60°C)TO 150°F (66°C) SHOULD BE MAXIMUM WATERTEMPERATURE MAINTAINED IN THE PRE-HEATERS.120°F (49°C) SHOULD
27NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C) WATER CIRCULATION.INSTALL ON OR CLOSE TO DISHWASHER. TOGGLE SWITCH MUST BECLOSED (ON) DURING THE RIN
28MANIFOLD KITSPrecision cut type “L” all copper A.O. Smith manifold kits assure water flow balance of all units. Without this balance, the full water
29CHECKLIST AND SERVICE INFORMATIONIMPORTANTThe installer may be able to observe and correct certain problems whichmight arise when the unit is put in
3 DANGERTHIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE THERMOSTATTO CONTROL WATER TEMPERATURE. HOT WATER TEMPERATURESREQUIRED FOR AUTOMATIC DISHWAS
30MOTOR WILL NOT RUN1. Confirm 120V AC to the controller. Also, to verify correct polarity, checkfor 120 V AC between hot supply and ground.If there i
31Model BTH Limited WarrantyA. O. Smith Corporation, the warrantor, extends the following LIMITED WARRANTY to the owner of this water heater.1. THE TA
32A.O. SMITH WATER PRODUCTS COMPANY5621 W. 115TH STREET • ALSIP, ILLINOIS 60803PHONE: 1-800-433-2545 • FAX: 1-800-433-2515 www.hotwater.com • E-MAIL:
4that the water temperature be set for the lowest temperature which satisfiesyour hot water needs. This will also provide the most energy efficientope
5• Do not cover the temperature & pressure relief valve.• Do not cover the instruction manual. Keep it on the side of thewater heater or nearby fo
6less than 100 square inches (645 cm²).If the confined space is within a building of tight construction, air for combustionand ventilation must be obt
7FIGURE 5*NOTE: BTH 250 USES TEE ONAIR INTAKE TERMINALDIRECT VENTHORIZONTAL VENTFIGURE 6DO NOT TERMINATE EXHAUSTOVER PUBLIC AREA WHERECONDENSATE OR
8TRANSMITTED INTO THE LIVING SPACES.IMPORTANTThe vent system must terminate so that proper clearances are maintainedas cited in local codes or the lat
9FIGURE 9IMPORTANTWHEN LOCATING THE TERMINALS ON A SIDEWALL, THE FOLLOWINGSPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BEFOLLOWED.1. The intak